Automatic tracking and positioning jet fire extinguishing system.
Using infrared, digital image, or other fire detection components to detect fire, temperature and
other early fire automatic tracking and positioning, and using automatic control mode to achieve
a variety of indoor and outdoor fixed jet fire extinguishing systems. The system consists of a fire
extinguishing device with a detection component and an automatic control part and a fire liquid
supply part. The fire extinguishing device is divided into automatic tracking and positioning fire
monitor fire extinguishing device (hereinafter referred to as automatic fire monitor fire
extinguishing device) and automatic tracking and positioning jet fire extinguishing device
(hereinafter referred to as automatic jet fire extinguishing device)
InquiryThreefold guidance
Positioning error is limited to
pixel spacing and distribution
point of fire source temperature
Automatic tracking
Once found, lock it immediately
and track the moving
dynamically
Five compound
Five compound protection,
really full-automatic
Parameters of fire monitor (ZDMS0.9/30S-LZ II)
Working pressure:0.9MPa
Flow rate: 30L/s
Protection radius: 44m
Jet radius: 49m
Working voltage: 85-242VAC
Power consumption: Locating: max 8 watts
Scanning: max. 21 watts
Positioning time: ≤ the 30s
Fire extinguishing time: ≤3 mins
Horizontal protection angle: 0-360°
Installation height: 8-15m
Scope of application: General purpose industrial buildings and structures, high occupancy places, large space building, for example, airports, railway stations, museums, industrial plants, large shopping malls, large warehouses, power plants, coal mines, colleges, and universities, etc
Flag of the detection component
Product model: UV detection module: JTG-UV-LZ300, Product model: UV detection module: JTG-UV-LZ301, infrared thermal imaging detection module: IRC-LZ II